Circuit Breakers
1. Major function
To be assembled with circuit breaker to achieve over/under voltage protection
2. Parameters and performance
Rated operation voltage Ue: AC 240V, 50Hz;
Overvoltage operation setting value Uvo: 280V;
Rated insulation voltage Ui: 500V; Tripping characteristics: the release is assembled with NB1-63 series circuit breaker. When the applied voltage is reduced to 35%Ue or increased to 95% ~ 105% of the over-voltage setting value, the release should drive the circuit breaker to act. When the applied voltage is below 35%Ue or above 105% of the over-voltage setting value, the release should be able to prevent the circuit breaker from closing. When the supply voltage is above 85% Ue and below 95% of over-voltage setting value, the circuit breaker should be able to close normally. The upper limit of the applied voltage should be less than 110% over-voltage operation setting value. Mechanical and electrical life: the mechanical and electrical life after the release is assembled with the circuit breaker should be 4000 cycles, of which, 500 cycles for over-voltage trip
3. Assembly and installation of the product
OUVT-X1 can be assembled with NB1-63 series circuit breaker, with the assembly diagram shown below:

Product Information

  • Circuit Breakers

Product Identifiers

AIDAlgopix unique identifier
AIDESPHDH001
Copied!
As an affiliate partner with eBay, Amazon, and Walmart, we earn from qualifying purchases. This means that we may receive a commission when you purchase products through links on our site. This does not affect the price you pay and helps us continue to provide valuable content. We appreciate your support.